Lesson 7
Objectives:
Safety topic-Lockout/Tagout
- Authorized Employees
When servicing or performing maintenance
on equipment or machinery, you must be sure that the equipment
cannot unexpectedly start-up or release stored energy. How do
you do this? The procedure for isolating the energy sources is
called lockout/tagout.
As employees who service and perform maintenance
on the equipment in this facility, you need to know how to avoid
the dangers involved when hazardous energy sources are not locked
out and/or tagged out. You must know, understand, and perform
lockout/tagout properly.
Energy control procedures
Each piece of equipment or machine needs
its own lockout/tagout procedure. The procedure contains the
steps for shutting down, isolating, blocking and securing machines
or equipment to control hazardous energy.
Also, the procedure should include the
steps for placement, removal, and transfer of lockout/tagout
devices.
Finally, it should contain the requirements
for testing and verifying the effectiveness of the lockout/tagout
devices and other energy control measures.
An orderly shutdown must be used to avoid
any additional or increased hazards when the equipment is stopped.
Use the shut down procedures that are established for each individual
machine.
Locks
Lockout devices must be durable and substantial.
Locks are standardized for ease of recognition.
The lock must identify the person who applied
it. This can be done with a tag.
The use of someone else's lockout device
is prohibited.
Tags
Tags must be durable and substantial.
Tags are standardized for ease of recognition
including the print and format.
The attachment means for a tag must be:
- Non-reusable.
- ÝAttachable by hand.
- ÝSelf-locking.
- Non-releasable with an unlocking strength
of 50 pounds.
The attachment means must be equivalent
to a one-piece, all-environment-tolerant nylon cable tie.
The tag's legend includes statements such
as Do Not Start, Do Not Open, Do Not Close, Do Not Energize,
or Do Not Operate.
Employee training
OSHA regulations contain specific training
requirements for employees that are authorized to perform lockout/tagout
operations. At 29 CFR 1910.147(c)(7)(i)(A), the rule says that
each authorized employee must receive training in the recognition
of applicable hazardous energy sources, the type and magnitude
of the energy available in the workplace, and the methods and
means necessary for energy isolation and control.
Your employer will show you energy isolating
devices, locks, and tags that are used in your facility. They
will also reveiw the lockout/tagout procedure before requiring
you to be familiar with it's practice.
Where to go for more information
OSHA regulations at 29 CFR 1910.147, The
control of hazardous energy (lockout/tagout).
Electricity Transmission
- Describe Electricity Transmission
- Describe Electrical Power Distribution
within a plant
- Describe Hydroelectric Power
- BTMOSC
- Basic Math Continued
Definition of Transmission
For the purposes of this class Electrical
Power Transmission is the transmission of electrical power across
long distances. Electrical Distribution is the distribution of
electricity within a facility.
The voltages involved in electrical transmission
are very high.
Generation Plant
At the generation plant electricity moves
from the generator to a switchyard where it is transformed to
a higher voltage and sent on to the grid via a transmission line.
The transmission line voltage will be between 69 and 500 thousand
volts.
High Voltage
The voltage is high to cut line losses.
In accordance with ohms law the loss in a line is equal to the
resistance times the current squared or IxIxR. As the current
increases the power lost is squared. So, it is important to keep
the current as low as possible.
This is done by keeping the voltage as
high as possible. The generated power is 3 phase alternating
current. Three phases are used because it is the most efficient
method. In addition to the 3 phases the power company uses the
earth as a ground. If you look at the towers you will notice
the 3 phases and often a fourth wire higher up. This is a ground
wire intended to attract lightning and protect the system.
In order to handle the high voltage the
transmission lines must be elevated and separated from each other.
Also the lines must be held in place mechanically by insulators
with the mechanical strength and electrical resistance necessary
for this purpose.
An interesting feature of the insulators
is how the electrical surface resistance is increased by the
design. Look at slide 7-2. Notice that the insulator has been
designed to provide the maximum possible surface distance between
the two ends This is because the insulator must be as long as
possible to provide maximum insulation.
Transformation
The voltage produced by the generator itself
is relatively low, probably 7200 volts or less. Why? Because
the generators windings are closely wound an extremely high voltage
in the generator would cause arcing. So, the generator has a
lower voltage and a higher current.
This power is presented to a transformer
in the yard which then steps the voltage up to distribution line
voltages. The transformer has two windings, the primary and the
secondary. If the primary had 100 windings and the secondary
had 200 windings then the transformer would double the voltage.
Grid
Look at slide 7.3 The transmission line
exits the switchyard and is presented to the power distribution
grid. The grid connects power plants and consumers within a geographical
area, such as a state or several states. Because the grid has
multiple power plants connected it allows the continuous flow
and shifting of power from one area to another to make sure there
is adequate power for customers at all times.
Typically it is economical to transmit
electricity over distances of up to 300 miles. Near customers
the transmission line enters a substation where high voltages
are transformed to distribution voltages of 34,500 volts or less
and sent to final customers where it is transformed one last
time to the final voltage.
Protective Relays
Protective relays are a type of sensor
located in black boxes at every substation. When a line is shorted
or broken, the relays shut off power on both ends of the line.
The grid's relays de-energizes faulted
equipment within 3/60th of a second, or 3 cycles.
It is vital that the fault gets turned
off instantaneously, because it sucks out wattage from other
parts of the system to feed its leak, causing a shortage to be
felt around the region.
Usually each relay must be checked once
every 2 to 3 years. On the scheduled maintenance date, the craftsman
drives to the substation with computer and test equipment in
hand. The craftsman checks the relays, reads the meters' output
and installs new equipment if necessary.
Power System Control SCADA (System Control
and Data Acquisition)
The grid is constantly monitored to make
sure it is functioning properly and power is being delivered.
SCADA equipment provides the telemetry
link for these functions. This large network connects every substation
on the grid.
This SCADA equipment detects signals, data
and disturbances.
For example remotely monitored meters measure
the amount of power sold to customers in order to correctly bill
them. The number of kilowatt-hours being used at a substation
is sent to Central Control for billing of large customers.
Protective relays already mentioned above
connected to the SCADA system constantly monitor conditions and
send alerts to distant control centers.
Likewise, the number of megawatts of load
on a transmission line is sent to the control center for load
control.
If there's sudden jump in the load, a signal
may be sent to the Generation plants to generate more power.
Another system monitors alarms at each substation and sends the
information to control centers to check the status of equipment.
Microwave stations, UHF, fiber optic and
voice are all used.
Electrical Power Distribution
This course element addresses the distribution
of power within a plant. We will use a typical pipeline pump
station as our example.
When power is generated locally at a plant
or imported from a utility it must be distributed within the
facility. The electrical equipment for this purpose will be referred
to as the distribution system.
Features of the distribution system.
1 Three phase AC power 480 volts : The
most common voltage used in the processing industries.Commonly
used on motors from 1/2 to 500 horsepower, when higher power
is required, higher voltage motors are employed.
2 Motor Control Centers : These enclosures
are protected from the elements and the process itself. This
part of the distribution system commonly contains transformers,
magnetic motor starters, variable frequency drives, main dis-connects,
and other electronic equipment that can be environment sensitive.
3 Power Buses : The main conductors used
in the distribution system.
4 Redundant cabling: provides a second
power path when needed .
5 A load shed/readd system: This system
is used for controlling the power use on the grid. Without some
way to control load, black-outs would be inevitable, causeing
major disruption to the process.
6 Uninterruptible power for critical control
systems: UPS systems generally are battery powered inverters
that assure constant power for computers and other critical control
systems that would be adversly affected by a loss of power.
7 Protective circuit breakers : These devices
are designed for equipment and personal protection. In the case
of an electric motor, the current limiting device would trip
before maximum amps were drawn, damaging the motor.In the case
of a GFI of ground fault interruption device, a ground fault
would be sensed before the current potential was high enough
to cause physical harm.
8 Lifeline generators: These units supply
backup power for the plant's lighing and ventilation systems.
Three phase AC power 480 volts
Plant power consists of 3 phase 480 volts
AC. This is because the plant has a large number of electrical
motors and the best power for electrical motors is 3 phase. 3
phase power provides high torque for starting. Motors are used
to operate support pumps and ventilation fans.
Motor Control Centers
The plant is organized into motor control
centers. Each area of the plant has a motor control center which
distributes power out to the actual end devices.
The motor control centers also contain
most of the control relays. For example a motor control center
would contain the relay which turns off ventilation fans when
a fire is detected.
Each major device powered/controlled by
the MCC has an assigned "bucket". The bucket is a hollow
box frame which is mounted on the MCC.

The bucket has an access door. On the door
would be indicator lights, a circuit breaker switch and perhaps
a on/off/auto switch to program the devices function. Some devices
are started automatically, for example a sump pump. The on/off/auto
switch overides the automatic control. It would allow the operator
to force the pump off or on for special reasons. Inside the bucket
itself are the motor starter and other controls. The motor starter
is energized by a small control voltage. When the motor starter
is energized its output contacts complete the 480 volt circuit
to the final device.
When we talk about load sheds we will see
that this function is implemented at the MCC.
Power Buses
Power buses provide the connection between
the generator and the Switchgear and within the Switchgear itself.
The bus is constructed from large copper bars mounted in the
Switchgear. Connections from the generators and Switchgear components
are made to the bus.
Redundant cabling to provide a second
power path when needed
The power is sent directly from the power
bus to the MCC via heavy cables. A second set of cables is also
routed to the MCC but by a different route. Hand operated breaker
switches are set to select one path or the other but never both
at the same time. This second route would be used after a disaster
thus preventing a fire or other problem from disabling the system
for a long period of time.
A load shed/readd system
A plant may have 2 out of 4 generators
on the power bus at the same time. A sudden generator failure
would bring the whole system down due to overloading the remaining
on line generator. To prevent this a smart controller detects
the generator failure and sheds non critical load at the MCC's.
Then the controller starts another generator, loads it and then
readds the loads which had been shed.
Uninterruptible power for critical control
systems
Some systems such as communications, station
control panels, and fire suppression are so critical that they
can never be shutdown. A UPS provides constant power to these
systems. Normally the UPS is powered by the stations generators.
When the generators shut down the UPS draws power from a battery,
converts it to AC and applies it to the critical loads.
Protective circuit breakers
All loads are protected by circuit breakers.
These circuit breakers are normally located at the MCC. Circuit
breakers trip open when an overcurrent occurs. Some of these
breakers weigh hundreds of pounds and break huge currents, thousands
of amps. The breakers are complex mechanical devices and require
a high level of skill to maintain.
Lifeline generators
At a remote plant like a pump station one
generator is located far from the others. This is to prevent
a generator room fire from destroying all possible generators.
These special generators are in their own rooms or outside and
are called lifeline generators. They are to provide life support
in the harsh arctic environment during emergencies.
Hydroelectric Power
Hydroelectric Power is a renewable resource.
Hydropower provides about 96 percent of the renewable energy
in the United States.
Other renewable resources include geothermal,
wave, power, tidal power, wind power, and solar power.
Hydroelectric powerplants do not use up
resources to create electricity nor do they pollute the air,
land, or water, as other powerplants may.
Hydroelectric power comes from the flowing
waters of winter and spring runoff from mountain streams and
clear lakes. Water, when it is falling by the force of gravity,
can be used to turn turbines and generators that produce electricity.
In the 1920's, hydroelectric plants supplied
as much as 40 percent of the electric energy produced. Hydroelectric
power presently supplies about 11 percent of the electrical generating
capacity of the United States. Hydropower responds quickly to
rapidly varying loads or system disturbances, which base load
plants with steam systems powered by combustion or nuclear processes
cannot accommodate.
58 powerplants throughout the Western United
States produce an average of 42 billion kWh (kilowatt-hours)
per year, enough to meet the residential needs of more than 14
million people.
This is the electrical energy equivalent
of about 72 million barrels of oil.
The efficiency of today's hydroelectric
plant is about 90 percent. Hydroelectric projects have long lives
relative to other forms of energy generation, and hydroelectric
generators respond quickly to changing system conditions.
HOW HYDROPOWER WORKS
Hydroelectric power is a form of
solar energy powered by the sun.
Generating Power
To generate electricity, water must be
in motion. This is kinetic (moving) energy. When flowing water
turns blades in a turbine, the form is changed to mechanical
(machine) energy. The turbine turns the generator rotor.
Some powerplants are located on rivers,
streams, and canals, but for a reliable water supply, dams are
needed. Dams store water for later release for such purposes
as irrigation, domestic and industrial use, and power generation.
The reservoir acts much like a battery, storing water to be released
as needed to generate power..The dam creates a "HEAD"
or height from which water flows. A pipe (penstock) carries the
water from the reservoir to the turbine. The fast-moving water
spins the turbine.
How Power is Computed
The actual output of energy at a dam is
determined by the volume of water released (discharge) and the
vertical distance the water falls (head). So, a given amount
of water falling a given distance will produce a certain amount
of energy. The head and the discharge at the power site and the
desired rotational speed of the generator determine the type
of turbine to be used.
This pressure is measured in pounds per
square inch. More head or faster flowing water means more power..
Turbines
There are two basic types of turbines (impulse
and reaction), with many variations.

A reaction turbine is a horizontal or vertical
wheel that operates with the wheel completely submerged, a feature
which reduces turbulence. In theory, the reaction turbine works
like a rotating lawn sprinkler where water at a central point
is under pressure and escapes from the ends of the blades, causing
rotation. Reaction turbines are the type most widely used.
An impulse turbine is a horizontal or vertical
wheel that uses the kinetic energy of water striking its buckets
or blades to cause rotation. The wheel is covered by a housing
and the buckets or blades are shaped so they turn the flow of
water about 170 degrees inside the housing. After turning the
blades or buckets, the water falls to the bottom of the wheel
housing and flows out.
Environmental Effects
Hydropower is not free from adverse environmental
effects. Considerable efforts have been made to reduce environmental
problems associated with hydropower operations, such as providing
safe fish passage and improved water quality.
Low-head Hydropower
A low-head dam is one with a water drop
of less than 65 feet and a generating capacity less than 15,000
kW. Large, high-head dams can produce more power at lower costs
than low-head dams, but construction of large dams may be limited
by lack of suitable sites, by environmental considerations, or
by economic conditions. In contrast, there are many existing
small dams and drops in elevation along canals where small generating
plants could be installed. New low-head dams could be built to
increase output as well. The key to the usefulness of such units
is their ability to generate power near where it is needed, reducing
the power inevitably lost during transmission..
Peaking with Hydropower
Demands for power vary greatly during the
day and night. These demands vary considerably from season to
season, as well.
Nuclear and fossil fuel plants are not
efficient for producing power for the short periods of increased
demand during peak periods. Their operational requirements and
their long startup times make them more efficient for meeting
baseload needs.
Since hydroelectric generators can be started
or stopped almost instantly, hydropower is more responsive than
most other energy sources for meeting peak demands. Water can
be stored overnight in a reservoir until needed during the day,
and then released through turbines to generate power to help
supply the peakload demand.
Pumped Storage
Like peaking, pumped storage is a method
of keeping water in reserve for peak period power demands. Pumped
storage is water pumped to a storage pool above the powerplant
at a time when customer demand for energy is low, such as during
the middle of the night. The water is then allowed to flow back
through the turbine-generators at times when demand is high and
a heavy load is place on the system.
The reservoir acts much like a battery,
storing power in the form of water when demands are low and producing
maximum power during daily and seasonal peak periods. An advantage
of pumped storage is that hydroelectric generating units are
able to start up quickly and make rapid adjustments in output.
They operate efficiently when used for one hour or several hours.
Future Potential
The hydropower resource assessment by the
Department of Energys Hydropower Program has identified 5,677
sites in the United States with acceptable undeveloped hydropower
potential. These sites have a modeled undeveloped capacity of
about 30,000 MW. This represents about 40 percent of the existing
conventional hydropower capacity.
Basic Terms
of Maintenance, Operations and System Components
Alternating Current An electric current changing regularly from one
direction to the opposite.
Ampere The
common unit of measurement of electrical current.
Baseload The
minimum constant amount of load connected to the power system
over a given time period, usually on a monthly, seasonal, or
yearly basis.
Baseload Plant
A plant, usually housing high-efficiency steam-electric units,
which is normally operated to take all or part of the minimum
load of a system, and which consequently produces electricity
at an essentially constant rate and runs continuously. These
units are operated to maximize system mechanical and thermal
efficiency and minimize system operating costs.
Bus (buswork) A
conductor, or group of conductors, that serve as a common connection
for two or more electrical circuits. In powerplants, buswork
comprises the three rigid single-phase connectors that interconnect
the generator and the step-up transformer(s).
Capacity The
amount of electric power delivered or required for which a generator,
turbine, transformer, transmission circuit, station, or system
is rated by the manufacturer.
Circuit
A conductor or a system of conductors through which electric
current flows.
Current (Electric)
A flow of electrons in an electrical conductor. The strength
or rate of movement of the electricity is measured in amperes.
Dam A
massive wall or structure built across a valley or river for
storing water..
Demand The
rate at which electric energy is delivered to or by a system,
part of a system, or a piece of equipment. It is expressed in
kilowatts, kilovolt amperes, or other suitable units at a given
instant or averaged over any designated period of time. The primary
source of "demand" is the power-consuming equipment
of the customers.
Direct Current
Electric current going in one direction only.
Distribution System The portion of an electric system that is dedicated
to delivering electric energy to an end user. The distribution
system "steps down" power from high-voltage transmission
lines to a level that can be used in homes and businesses.
Generator A
machine that converts mechanical energy into electrical energy.
Head The
difference in elevation between the headwater surface above and
the tailwater surface below a hydroelectric powerplant under
specified conditions.
Hydroelectric Power Electric current produced from water power.
Hydroelectric Powerplant A building in which turbines are operated, to drive
generators, by the energy of natural or artificial waterfalls
Kilowatt-Hour (kWh) The unit of electrical energy commonly used in
marketing electric power; the energy produced by 1 kilowatt acting
for one hour. Ten 100-watt light bulbs burning for one hour would
consume one kilowatt hour of electricity.
Kinetic Energy
Energy which a moving body has because of its motion, dependent
on its mass and the rate at which it is moving.
Load (Electric)
The amount of electric power delivered or required at any specific
point or points on a system. The requirement originates at the
energy-consuming equipment of the consumers.
Megawatt
A unit of power equal to one million watts. For example, it's
the amount of electric energy required to light 10,000 100-watt
bulbs.
Ohm The
unit of measurement of electrical resistance. The resistance
of a circuit in which a potential difference of one volt produces
a current of one ampere.
Peakload The
greatest amount of power given out or taken in by a machine or
power distribution system in a given time.
Pumped-Storage A
plant that usually generates electric energy during peak-load
periods by using water previously pumped into an elevated storage
reservoir during off-peak periods when excess generating capacity
is available to do so. When additional generating capacity is
needed, the water can be released from the reservoir through
a conduit to turbine generators located in a power plant at a
lower level.
Reservoir An
artificial lake into which water flows and is stored for future
use.
Volt (V)
The unit of electromotive force or potential difference that
will cause a current of one ampere to flow through a conductor
with a resistance of one ohm.
Watt (W)
The unit used to measure production/usage rate of all types of
energy; the unit for power. The rate of energy transfer equivalent
to one ampere flowing under a pressure of one volt at unity power
factor.
Watthour (Wh)
The unit of energy equal to the work done by one watt in one
hour.
Go to the basic math link and study
pages 56 thru 60. Session 7 quiz will contain questions on this
material.
Delta Mine Training Center
Copyright © 2001 DMTC. All rights reserved..
|